4 Pole Contactors AC Controlled Utilisation category AC1 Auxiliary contact configuration one N/O, one N/C Width of LC1D contactors is 45mm Closing time of LC1D series is 12-22ms, opening time is 4-19ms These contactors must not be used with TeSys overload relays, interconnection units or GV2 circuit breakers Approvals UL and CSA

Schneider Electric Tesys D LC1D 4 Pole Contactor, 2NO/2NC, 25 A, 230 V ac Coil

Manufacturer:
Manufacturer Part No:
LC1D128P7
Enrgtech Part No:
ET13863517
Warranty:
Manufacturer
£ 82.75
Checking for live stock
Coil Voltage:
230 V ac
Pole and Throw Configuration:
4P
Width:
45mm
Range:
TeSys D
Input Current:
25A
Contact Current Rating:
25 A
Maximum Operating Temperature:
+60°C
Terminal Type:
Screw
Control Voltage:
230 V ac
Length:
85mm
Better World Verification:
Green Premium
Better World Product:
Yes
Series:
LC1D
Depth:
90mm
Mounting Style:
Plate, Rail Mounting
Number Of Auxiliary Contacts:
2
Normal State Configuration:
2NO + 2NC
Auxiliary Contact Configuration:
1NO + 1NC
Contact Voltage Rating:
690 V ac
Number of Poles:
4
Minimum Operating Temperature:
-5°C
RoHS Status:
ROHS3 Compliant
Coil Voltage:
230VAC
Termination Style:
Screw Terminal
Operating Temperature:
-40°C ~ 70°C
Coil Resistance:
-
Switching Voltage:
690VAC, 300VDC - Max
Coil Power:
-
REACH Status:
REACH Unaffected
Must Operate Voltage:
184 VAC
Contact Form:
4PST-2NO/2NC (2 Form A, 2 Form B)
Moisture Sensitivity Level (MSL):
Not Applicable
Operate Time:
22 ms
Must Release Voltage:
69 VAC
standardLeadTime:
5 Weeks
Contact Rating (Current):
25 A
Features:
Auxiliary Contacts
Mounting Type:
Chassis Mount, DIN Rail
Series:
TeSys
title:
LC1D128P7
Release Time:
19 ms
Packaging:
Box
Contact Material:
-
pdf icon
Green Premium - Product Environmental Profile(Technical Reference)
pdf icon
Instruction Sheet - LC1 / LC2 D115 D150(Technical Reference)
pdf icon
UL E164862(Technical Reference)
pdf icon
CSA 43364(Technical Reference)
pdf icon
Catalog 2023(Technical Reference)
pdf icon
Datasheet_LC1D128P7(Technical Reference)
pdf icon
Product Change Notice (PCN)(Technical Reference)



Product Reviews