VB6/VB7 - Compact Rreversing Contactors
The mechanical lock between the two contactors prevents one of the contactors from switching on, as long as the other is still switched on and vice versa.
Switching over reversing contactors too quickly poses the risk of a phase short circuit.
This is the case if the arc of the contactor switching off has not yet extinguished and the contacts of the contactor switching on are already closed.
To avoid this risk, the two contactor coils must be switched to idle for a minimum of 50 ms during the switchover process and electrically locked against each other.
Technical specifications
Rated operating voltage:
220 to 240Vac
Mechanical lifespan:
10 m switching cycles
Ambient temperature:
-25°C to +55°C
Selection guide
Type
Auxiliary switch
Motor rating (AC2/3)
Motor rating (AC2/3)
220/240V
380/440V
VB 6-30-10
1 NO
2.2 kW
4kW
VB 6-30-01
1 NC
2.2 kW
4kW
VB 7-30-10
1 NO
3kW
5.5kW
VB 7-30-01
1 NC
3kW
5.5kW


ABB 2CDS252001R0164 System M Pro S200 MCB Mini Circuit Breaker 2P, 16 A, 6 kA, Curve C
Manufacturer:
ABBManufacturer Part No:
2CDS252001R0164
Enrgtech Part No:
ET13833426
Warranty:
Manufacturer
£ 52.03
Checking for live stock
Current Rating:
16 A
Series:
S200
Range:
System M Pro
Tripping Characteristics:
Type C
Depth:
69mm
Rated AC Voltage:
400 V
Breaking Capacity:
6 kA
Number of Poles:
2