857-800 Wago 857 Series Signal Conditioner, Current, Voltage Input, Current, Voltage Output, 24V dc Supply

Wago Series 857 Signal Conditioner, 0 to 5V, Voltage Output Signal Type - 857-800 This temperature signal conditioner by Wago is designed for RTD sensors, offering precise current and voltage output signals. With configuration options via DIP switch and a supply voltage of 24 V DC, this compact 6 mm module is ideal for industrial applications. Features & Benefits • Compatible with Pt100, Pt200, Pt500, and Pt1000 sensors, as well as resistors up to 4.5 kOhm
• 2-, 3-, and 4-wire connection technology for versatile installations
• Calibrated switching between measurement ranges for accurate readings
• Built-in detection of sensor wire break/short circuits and measurement range underflow/overflow for enhanced safety
• Clipping capability for limiting analog signal output
• Safe 3-way isolation with 2.5 kV test voltage per EN 61140 for added protection Applications • Suitable for temperature sensing in industrial automation
• Ideal for monitoring and control systems in electrical and mechanical industries
• Can be used for converting temperature signals into standard analogue signals
• Used for precise measurement of temperature ranges in demanding environments Q: Can it detect sensor wire breakage? Yes, it is equipped to detect sensor wire break/short circuits for added safety. Will it work with Pt100 sensors? Yes, it is compatible with Pt100 sensors for accurate temperature measurements. Is it suitable for industrial use? Yes, it is designed for industrial applications with reliable performance.

Wago 857 Series Signal Conditioner, Current, Voltage Input, Current, Voltage Output, 24V dc Supply

Manufacturer:
Manufacturer Part No:
857-800
Enrgtech Part No:
ET24125817
Warranty:
Manufacturer
£ 128.61
Checking for live stock
Module Type:
Signal Conditioner
Input Signal Type:
Current, Voltage
Output Signal Type:
Current, Voltage
Input Range:
0 → 1kΩ
Output Range:
0 → 5 V, 0 → 10 V, 1 → 5 V, 2 → 10 V
Supply Voltage:
24V dc
Mounting Type:
DIN Rail
Operating Temperature Range:
-25 → +70°C
Series:
857
Standards Met:
EAC
Maximum Operating Temperature:
+70°C
Termination:
Cage Clamp
Minimum Operating Temperature:
-25°C
Signal Conditioner Function:
Converting
pdf icon
Datasheet - 857-800-aaf02744(datasheets)
pdf icon
Instruction Sheet - 857-800-16297071(datasheets)
pdf icon
NOTICE This product is not for general use by consumers-7e2ee795(datasheets)



Product Reviews